Chexit goes into alarm, no led light, no delayed egress

RELATED FAQS

Question
Answer
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears.  After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...
Followings could cause the Chexit device to go into alarm after the rearm time: Chexit devices shipped after 8-24-2015 with motor driven: Module DPS LED is ON DPS switch contact is open: Close t...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: Chexit device has a RX switch with a connector that needs to be connected to the Chexit module otherwise the alarm will sound af...
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...
The following could cause the Von Duprin CX solenoid ( devices shipped prior to 8-24-2015) to pull and drop and sound the alarm with solid LED light. Wrong power supply, requires Von Duprin ...
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...
The following could cause the Chexit device shipped prior to 8-24-2015 with solenoid driven to go into weak alarm with solid LED light: Wrong power supply- Chexit device requires  a...
There is no conversion kit for Von Duprin Chexit device.  If delayed egress Chexit device is required, the entire device must be replaced.