chexit and EL

RELATED FAQS

Question
Answer
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
You can not use these options together on the same device per the following reasons: QEL/EL device retracts the latch bolt of the exit device allowing entry. CX (Chexit) device ...
The hole should be drilled in the field once the end cap is located on the door.  It is a 5/8" hole, that is located 5/16" from the end of the mechanism case. See installation instruction of t...
The EL Wiring Adapter is not needed for a CX device.