Question
Answer
The PIB300/PIB301 should be located as close as possible to the Access Control Panel.  Do not exceed 500 feet.
Wiring distance from the PIB300/301 to the AD300/301 locksets may be up to 1000 feet (18AWG) for Power and up to 4000 feet (24AWG) for the RS485 data lines.
See the User Guide instructions in the links below
Some Access Control Panels are designed with “Supervised” or “Dry contact” requirements for the inputs and have no common ground between the ACP (Access Control Panel) and device at the door. “S...
Schlage offers the “RLBD” to support these supervised or dry contact interface applications. The "RLBD" plugs directly into the PIM400-TD2 or PIB300-TD2 for easy hook-up.  
Please reference this Tehnical Note RLBD SES-20120418 for RLBD setup, use information, hook-up diagrams and some testing suggestions when connecting to a Supervised dry contact Access Contro...
This is a link to the RLBD Installation Instructions.
This RLBD data sheet can also be found at Schlage/Technical Support. RLBD DataSheet
Dynamic Channel Switching is a feature of the Schlage AD-series wireless access point modules. Dynamic Channel Switching (DCS) increases the robustness of the wireless RF communication in a noisy r...
  Here is a Technical Note on what Dynamic Channel Switching is, what it improves, how to set-up, and frequently asked DCS questions. DCS Tech Note here  
Setting Dynamic Channel Switching   1)     Connect and couple the SUS to the PIM400 you intend to change. See the SUS User Guide for details   2)     Under “PIM Properties” and the “Edit” tab is ...
The following common wiring diagrams are available:One Single Door with Panic BarElectric Latch Retraction, with Auto OperatorDelayed egress - Fire Rated ApplicationAuto Operator and actuatorElectr...
Electronic Protocols:Access Control Door with electric trimAccess Control with electric strike Access control with electric strike and LCN 4600 automatic operatorAccess Control with remote Loc...