can you lead line frame with hospital stops

RELATED FAQS

Question
Answer
Yes, hospital stops are available on fire rated frames. Maximum approval = 3 hour Maximum sizes:  singles up to 4'0" x 8'0" pairs up to 8'0" x 8'0" Maximum hospital stop height 6" from bot...
Hospital Stops are located at the bottom of the frame jambs and/or mullions. The integral door stops are terminates above floor line and is closed with a 45° or 90° angle to facilitate cleaning at ...
Lead lined frames are intended for use in the X-ray Room locations in Health Care facilities. Frames are provided by Steelcraft prepped as follows:  Frames are supplied knock-down (KD). Fram...
Radiation, Lead Lined
Hospital Stops are available as either: 45° Hospital Stop - the stop of the frame terminates at a 45° angle 90° Hospital Stop - the stop of the frame terminates at a 90° angle The type of hos...
The determination was made that Lead Lined covers are no longer needed for the LCN product line, see below Marketing/EHS document. Lead Lined cover discontinuation letter
Ives does not offer a continuous hinge designed specifically for lead lined doors.  Standard hinges may work if the hinge and mounting hardware do not penetrate the lead lining in the door.&nb...
Ives does not offer any lead lined pivots.  Some of the Ives pivots can be used on lead lined doors such as the 7230F, 7237F, 7230F/7237F Int.  The hole pattern for the mounting screws are offs...