Can fire rated doors be prepped for electric latch retraction
”
RELATED FAQS
Question
Answer
Can fire rated exit devices have electric latch retraction?
Resolution:
Yes, fire rated exit devices can have electric latch retraction. However, the devices must be tied into a fire alarm system to remove power from the units so the doors will be latched in the ...:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
What Steelcraft doors can be prepped for a Von Duprin InPact device?
Resolution:
Steelcraft L-Series and T-Series doors are available (as an option) factory prepared for the Von Duprin InPact exit device. :
Can a 3 hour A labeled Fire Door be prepped for multiple glass lights?
Resolution:
A fire rated door for 3 hours can have one glass light maximum: 100 square inches and must have an approved glass (Firelite type) Max glass size cannot exceed 12" in width or 33" in height. Wi...:
Can Steelcraft doors be prepped for the 98/9949 Concealed Vertical Cable Exit Device?
Resolution:
Yes, as an option, Steelcraft doors are available with factory prepared for the 98/9949 Concealed Vertical Cable Exit Device.L, B, CE, T and CE-Series doors are available factory preparedDoor prepa...:
What strike do I use with a Von Duprin rim device on a pair of doors with flush bolts?
Resolution:
NON Fire Rated doors would use the 1609 strike applied to the inactive leaf with flushbolts. This may NOT be used on Fire Rated openings.:
Common wiring diagrams
Resolution:
Electronic Protocols: Access Control Door with electric trim Access Control with electric strike Access control with electric strike and LCN 460...: