Can EL exit be held open electrically by access control system
”
RELATED FAQS
Question
Answer
Can the Von Duprin EL option be added to any existing 98/99 device?
Resolution:
The Von Duprin EL option can be added to any existing 33A/35A, 98/99 series exit devices. :
Can the Von Duprin exit alarm ALK and electric latch retraction QEL or EL device be in the same device?
Resolution:
No, Von Duprin exit alarm ALK and electric latch retraction QEL or EL are installed in the same location and can't be ordered together with the same device.:
What is needed to keep the EL device retracted all day?
Resolution:
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...: