can an exit device have electric strike

RELATED FAQS

Question
Answer
The Von Duprin 6111 electric strike would work with DOM 1790 device on medium style doors Centerline of the 1790 device mounting screws are located 1 11/16" from face of stop. See d...
This is not a recommended application as the electric strike does not have the same holding force as the XP98/99 rim exit device. The electric strike has 1500 pounds of holding force whereas the XP...
Von Duprin does not recommend using XP98/99 devices with any electric strike.   Von Duprin recommends using the standard 98/99 rim device.  The XP device has 2000 pound holding forc...
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount el...
The 5100 electric strikes are for use with cylindrical locks only.  Instead use the following:6211 electric strike is used with mortise lock without deadbolt on a new single door, hollow ...
You can use the surface mounted 6300 electric strike with 33A/35A rim exit device as long as you have enough stile width for this strike.
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F,...