Can an AD be powered by aux power

RELATED FAQS

Question
Answer
Use a multi-meter in series with the batteries to measure battery current.  Be sure your multi-meter can accurately measure very low current, in the micro-amp range. See the attached Technical Not...
All Keypad ONLY credentials with firmware versions between 2.9.2 and 2.11.0 should be updated to the latest firmware available at www.schlage,com/support.
A firmware issue with Keypad ONLY credential firmware, versions 2.9.2 through 2.11.0 and manufactured between 9-9-2010 and 1-5-2011 will exhibit poor battery life.
The Keypad ONLY credential Reader (KP) can prevent the reader from entering its low power sleep mode - with firmware versions 2.9.2 through 2.11.0
A Technical Note has been generated to document one method of measuring battery current. See the attachment HERE.
AD300 locksets MUST have hard power to operate.
Connect 12VDC or 24VDC power supply to the AD300 lock before attempting HHD communication.
The Schlage AD/CO trims are not compatible with the Falcon 25-V device due to the main cam on the device rotating the opposite direction for a given hand compared to the AD/CO trims output dri...
The AD-Series locks provide screw terminals on the main PCB where hardwired power may be applied.
Use of hardwired power with any product other than the AD300, is NOT recommended.
The HHD Kit and Schlage Utility Software will not know or warn our customers about Power Fail considerations (will ALWAYS power fail AS IS) if hardpower is appied.
    The super capacitor powers the AD300 motor to the correct power fail position, secure or unsecure, during a power fail event.     When power is restor...
    Recognize the AD300 when first powered, or when recovering from a power loss, may NOT be fully functional for two minutes until the AD300 super capacitor is fully recharged....
The Exit Only (EO) device will accept any 19 Series trim as the main cam for the trim input is always put on the device center case.