bypass potted circuit breaker

RELATED FAQS

Question
Answer
For Potted Modules shipped before August of 2012, you can test by applying power to the potted circuit breaker to and if good the following voltages will be seen: 23-24V DC on the gree...
The power to the Von Duprin potted module also called potted circuit breaker is non polarized.
The potted circuit breaker for the Von Duprin EL device does the switching from the 16 amp pull coil on the solenoid to the .33 amp holding coil of the solenoid.
One of the following items may cause the EL1690 device to retract then release: Incorrect power supply - Verify you have the PS873-2/4TD or PS914-2RS/4RL power supply. Problems with wire gauge...
Products shipped on or after August 8, 2012 no longer require the EL wiring adaptor. The ELK Wiring Adaptor (900ELK) was used only when using the PS914 power supply with either the 900-2RS or 900-...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...