are panic sets fire rated
”
RELATED FAQS
Question
Answer
Can a panic device be converted to a fire-rated device in the field?
Resolution:
A standard exit device can't be modified to a fire rated exit device. In order to get a product with the UL fire label, a new device must be purchased. This is a UL requirement.:
Where do I install my Auxiliary Fire Latch (AFL) in a Less Bottom Rod, Fire Rated (LBR-F) exit device?
Resolution:
Installation should be 6" from bottom of the door. See attached templates as reference. T-5494 for HM Doors W-5494 for Wood Doors:
What is the difference between Panic Hardware and Fire Exit Hardware?
Resolution:
The most obvious difference (in the device) is the lack of mechanical dogging on a Fire Rated Device. There are some internal parts that may be different and the method it is secured to the d...:
Common wiring diagrams
Resolution:
Electronic Protocols: Access Control Door with electric trim Access Control with electric strike Access control with electric strike and LCN 460...:
Is the 8827 available LBR?
Resolution:
Von Duprin offers a PL8827 LBR device with a pullman style top latch and Less Bottom Rod for use with electric strikes, but is not UL labeled nor ANSI/BHMA certified.:
How can I cover a 86 or 161 prepped door with a 19-R?
Resolution:
The 4170 cover plate can be used to cover the 86 & 161 prepped doors.:
What is the maximum size of a UL fire rated three (3) sided frame?
Resolution:
Fire Rated three (3) frames are available in the following maximum door opening sizes: F and FN-Series frame:4' 0" X 10' 0" single door opening8' 0" X 10' 0” double door openingMU-Series frame...: