Are door silencers required for fire rated steel doors?
”
RELATED FAQS
Question
Answer
Are intumescent seals or gaskets required on fire rated steel doors?
Resolution:
Intumescent seals or gaskets are not required on fire rated steel doors. Generally speaking, the requirement for intumescent seals or gaskets are a function of the individual manufacturers’ listi...:
Are astragals required on fire doors?
Resolution:
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...:
How do I order a Von Duprin mullion prepped for something other than our standard strikes?
Resolution:
To use Von Duprin mullion for something other than our standard strike, order the mullion "Blank" and prep in the field.:
Why are frames grouted?
Resolution:
Grouting frames is: A process done in the field during hollow metal frame installation The internal cavity of the frame is fill with masonry or mortar It is intended to mainly provide ...:
Are steel stiffeners required in all door constructions?
Resolution:
No, steel stiffeners are not required in Hollow Metal doors, they are one of many optional core available.Per ANSI/SDI A250.8 and ANSI/HMMA 867, core construction are optional offeri...:
Is the Von Duprin 6223 fire rated for pairs of wood doors?
Resolution:
The 6223-FSE electric strike is fire rated for pairs of wood doors, but check with wood door manufacturer to see if they have been approved for this application.:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.: