Allegion Electrical devices and power supplies

RELATED FAQS

Question
Answer
The 8200 Series operator CANNOT power a strike, maglock, or EL device. A separate power supply is ALWAYS required. There is an onboard relay to control a strike, maglock, or EL device.
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...
Electrical hinges or a power transfer units are the most commonly used practices to run electric power to locks and/or strikes. Electric Hinges: Most electric hinges will fit into a standard 4 ...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
Yes, 871-2 option board is included in the PS872 power supply and  will power 1 or 2 EL electric exit devices.
The 900-2RS option board is used with PS914 power supply to isolate the inputs such as key pads or card readers from the outputs for EL electric exit devices.  The EL draws 16 amp inrush that needs...
Option boards are not required with PS900 series power supplies when using electric strikes. See the list of options below. The PS902 would power up to 5 electric strikes at 24VDC or&n...