510-ULAC EIR will not output power
Resolution:
Ensure they have the physical EIR relay box plugged into the power supply. or the jumper from SW Gnd to DC- is in place. (Mutually exclusive)If one of theses is not in place the po...:
510ULAC EIR has no output power
Resolution:
510-ULAC EIR, has no power out of SW GND and DC+,Verify Fire alarm input provides closure across IN + and IN-, When the Fire alarm input opens shut off the DC output.:
How to setup a fire alarm reset for ton 515 power supply
Resolution:
see attached documentreset 515 Power Supply:
Can the Schlage 505 power supply use 2x 8 amp hour batteries for backup?
Resolution:
No. Those power supply charging circuits were designed for 2x 12v at 4 amp hour batteries. The charging circuit will not support those batteries.: