101+ or 390DEL After memory clear Relock delay may reset to 1 second.
Resolution:
If memory is cleared on delayed egress maglocks they may revert to a 1 second relock time. The relock delay will need to be reset to a value between 6 - 8 seconds. The max delay is 30 seconds.:
Does the 101+ or 390DEL require a spike supressor?
Resolution:
The 101+ and 390DEL mag locks have built in spike suppression. There should not be any type of diode, resistor, or supression put at terminals 1 and 2. can cause residual magnetism :
New Delay Egress Maglock Replacing the 390DEL and 101+
Resolution:
The 390DEL and 101+ maglocks have been discontinued. They are being replaced within the product line to the M490DE, a plunger-switch activated delayed egress maglock much like the 390DEL.:
101+ or 390DEL not locking
Resolution:
Check power at terminals 1 and 2 (12 or 24V AC/DC ).When lock has power but will not lock check dip switch SW4-7 (Automatic Relock) and ensure it is on.[101+ only] Ensure SW1 the red slide switch i...:
What is the material and finish of the 300 / 400 series mag lock armature?
Resolution:
The finish for the 300 / 400 mag series armatures is 4140 Chrome Moly Steel with a Nickel Plating.: