Allegion
Terms of Use
Privacy Policy
Frequently Asked Questions
Ask your question
Entering your question as a complete sentence will provide more accurate results than keywords or phrases.
User questions
FAQs
Category List
FAQs
«
232
233
234
235
236
»
Question
Answer
What is the part number for the cable or wiring harness for an E996L trim?
Resolution:
The part number for the cable or wiring harness for an E996L trim is CABLE.10038:
The CT5000 does not log reader tamper events.
Resolution:
Reader tamper switch monitoring was not available at product launch, but will be released shortly afterward.When reader tamper switch monitoring is implemented, a tamper signal from either reader w...:
Can the CT5000 be powered by AA alkaline batteries?
Resolution:
The power supply must be able to source enough current for the CT5000 (500 milliamps) plus any additional devices (electric strike, mag lock, etc.) connected to the CT5000.:
What is an A, B, C and D label fire door?
Resolution:
A = 3 hour (180 minute) fire ratingB = 1.5 hour (90 minute) fire ratingC = 0.75 hour (45 minute) fire ratingD = 0.5 hour (30 minute) fire rating:
If you remove jumper off the 900-FA board to install onto the 900-2RS should they give the jumper to the customer so they have it?
Resolution:
The removed jumper is left inside the power supply enclosure at the factory so it would be available if the FA card is ever removed.:
several red flashes on prox cards on cm locks; No access
Resolution:
Red LED blinks 2-3 times after a valid credential is presented.Out side of time zone.Verify corrected time on lock ensure cards are in a valid time zone.:
What is the maximum number of users on an AD-200 lock
Resolution:
AD-200 5000 users, 5000 audits CO-100 500 users CO-200 2000 users 2000 audits KC-2 1000 users, 1000 audits CM (Silver) 1000 users, 1000 audits:
Can the 268-10 or 320 Maglocks without circuit boards be wired for 12 or 24 VDC
Resolution:
(12VDC: Red ties to positive(+), White wire ties to negative(-), Black & Blue wires tied together) (24VDC: Red and Black wires tied together connect to positive(+), Blue and White wires t...:
Can Drywall Slip-on frames be welded?
Resolution:
Drywall Slip-on frames are recommended and designed to be installed as KD (Knock Down) assemblies and not recommended to be welded (SUA). If a DW-Series or K-Series is welded prior to installa...:
Is the Ives 8190 for 2 1/4" thick doors an engineering special?
Resolution:
The 8190 can be order as a standard for 2 1/4" door thickness. Specify the door thickness to get proper mounting hardware.:
«
232
233
234
235
236
»