Will the 9100 series Benchmark III power an electric strike?

The Benchmark III control has a 24VDC, 2.5 amp power supply, and built in relay for controlling electric strikes or other accessories less than 2.5 amps current load.

  • For a fail secure strike, run a jumper from 24VDC - (negative) to relay common. Then run a wire from NO relay (normally open)  to one wire on the electric strike.
  • For fail safe strike, run a jumper from 24VDC - (negative) to relay common. Then run a wire from NC relay (normally closed)  to one wire on the electric strike.