Wiring for the Gateway:
DC terminal input: 18AWG, 2 conductor (Belden 8760 or equivalent) up to 1000 ft (305 m)
Gateway to ACP: 24AWG, 2 or 4 conductor shielded (Belden 9842,9841 or equivalent) up to 4000 ft (1219 m)
Gateway to router: CAT3, CAT5/5E or CAT6 up to 328 ft (100 m)
The wiring must be done in parallel. A power source can lose output capability if multiple devices are used.