As of 20212, the NFPA 80 Chapter 5 details the following 13 fire door assembly inspection points:
1. Labels are present and legible
2. No holes or breaks in the door or frame
3. Glazing and glass kit/glass beads are intact and securely fastened
4. Door, frame, and hardware are in proper working order
5. No missing or broken parts
6. Door clearances are within allowable limits
7. Door closer/spring hinges are operational, and the door is self-closing
8. Coordinator ensures that door leaves close in proper sequence (applicable to pairs only.)
9. Door is self-latching in the closed position
10. Opening is not equipped with auxiliary items which interfere with operation
11. No field modifications have been performed that would void the label
12. Gasketing and edge seals where required are present, continuous, and of the proper type for a fire door.
13. Signage on doors covers less than 5% of door face and is not attached with metal fasteners.