PS873-2Q flashing green, QEL LED not on and not retracting?

If there is no LED blinking at the QEL device and access control is activated
  1. Make sure 24VDC is available at the QEL device
  2. If not check the voltage at the power supply and make sure 900-2Q board is providing 24VDC output into the device
  3. If 24VDC is available at the QEL motor with no LED then the QEL motor is defective.