Is there a part number for FA jumper (single red wire) for a 900 Series Power Supply?

The FA Jumper (two pin plug with single red wire) is not sold separately.

Without that jumper in place, the board will look for a 900-FA board installed in the 4 pin port nearby to determine if the board will have output power.

If the FA jumper was removed, add a 900-FA board with a single wire connecting the FA1 and FA2 terminals (if output is not required to discontinue during a fire alarm condition) or connect the Fire Alarm system as indicated in Schlage 900-FA Fire Alarm Input Installation Instructions (if output should be discontinued during a fire alarm condition).

 