How to disable delayed egress mode on the M490 DE/DEP

M490DE  -- suppress  delay function - 
Place a jumper across the Fire and AUX  inputs
Place dip switch SW2 - 4( Relock on FA clear or power up.) on and SW2-8 off (Plunger button disable)