How to configure a master slave unit together for 101-2+ to trigger from aux OR rocker inputs

When using a 101-2+  mag lock you need to make sure that dip switch #3 on switch SW4 is in the ON position, and that the rocker switch from the slave is connected to terminals #5&6 on the master. . This will configures the master unit to go into delayed egress when triggered by the rocker switch OR the aux inputs. The Black and Red fly leads factory installed on the master control board must be connected to the respective power inputs 1 and 2 of the slave unit.