How many Von Duprin QEL devices can be connected to a power supply?

Product Ordered after 7/10/2012 - Product identified by label on QEL motor

You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to operate the QEL+ devices. You can use either the 900-2RS or the 900-4RL boards to operate the new style or current QEL+ device. 

If a customer uses a power supply from another manufacturer, Von Duprin will still warranty all parts and components from the Von Duprin QEL exit device.  The warranty will be voided if the customer uses a power supply that does not meet the specification requirements of the QEL. 

"The new Von Duprin QEL requires a 24 volt, 2 amp regulated power supply. An option board/control switch is still required per the needs of the application, but the new QEL does not require a dedicated -2Q board. The QEL can be powered with any properly working 24V, 2 amp regulated power supply."

The attached table shows the number of QEL+ exit devices that can be used with PS900 series power supplies. An existing 900-2Q will operate the current QEL+ device. 

Power supply model number Number of QEL + devices Gauge & maximum wire run from power supply to each QEL+ exit device Gauge & maximum wire run from power supply to each QEL+ exit device Gauge & maximum. wire run from power supply to each QEL+ exit device Gauge & maximum wire run from power supply to each QEL+ exit device
PS902-2RS 1 or 2 18 gauge, 200' max   16 gauge, 320’ max   14 gauge, 500' max  12 gauge, 800' max  
PS904-2RS 1 or 2 18 gauge, 200' max  16 gauge, 320' max  14 gauge, 500' max  12 gauge, 800' max 
PS904-4RL 1 to 4 18 gauge, 200' max  16 gauge, 320' max  14 gauge, 500' max  12 gauge, 800' max 
PS906-2RS 1 or 2 18 gauge, 200' max  16 gauge, 320' max  14 gauge, 500' max  12 gauge, 800' max 
PS906-4RL 1 to 4 18 gauge, 200' max  16 gauge, 320' max  14 gauge, 500' max  12 gauge, 800' max 
PS906-4RL-4RL  1 to 8 18 gauge, 200' max  16 gauge, 320' max  14 gauge, 500' max  12 gauge, 800' max 
PS914-2RS 1 or 2 18 gauge, 200' max  16 gauge, 320' max  14 gauge, 500' max  12 gauge, 800' max 
PS914-4RL  1 to 4 18 gauge, 200' max  16 gauge, 320' max  14 gauge, 500' max  12 gauge, 800' max 

PS914-4RL-4RL:  1 to 8        If controlling 8 QEL devices,  consider contacting Von Duprin technical support to review the application.

Note: 2RS represents a 900-2RS board and 4RL represents a 900-4RL.



Product Ordered before 7/10/2012 - Product identified by no label on QEL motor.

You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices.  The attached table shows the number of QEL exit devices that can be used with PS900 series power supplies.

Power supply model number Number of QEL devices Gauge & maximum run wire from power supply to each QEL exit device
PS902-2Q 1 or 2 18 gauge, 200' max run wire
PS904-2Q 1 or 2 18 gauge, 200' max run wire
PS904-2Q-2Q 3 or 4 18 gauge, 200' max run wire
PS906-2Q 1 or 2 18 gauge, 200' max run wire
PS906-2Q-2Q 3 or 4 18 gauge, 200' max run wire
PS906-2Q-2Q-2Q 5 or 6 18 gauge, 200' max run wire
PS914-2Q 1 or 2 18 gauge, 200' max run wire
PS914-2Q-2Q 3 or 4 18 gauge, 200' max run wire

Note: 2Q represents a 900-2Q board