How many M996L/L-BE Trim can be connected to a PS902, PS904, PS906, PS914 power supply?

M996L/L-BE Summary:

The Von Duprin M996L/L-BE  trim is a motorized, electrified trim which can be locked or unlocked remotely.
The trim can be field configured as Fail Safe or Fail Secure, and automatically operates at either 12VDC or 24VDC.

M996L Current Requirements:

Fail Safe (FS):

  • 12V:  0.13A inrush, 10mA holding
  • 24V:  0.08A inrush, 10mA holding

Fail Secure (FSE):

  • 12V:  1.12A inrush,   10mA holding
  • 24V: 0.59A A inrush, 10mA holding
     

What Does Inrush Current Mean?

When M996L is powered, a 600ms "inrush" current is needed to charge a capacitor on the trim's circuit board.
Inrush current varies based upon power supply voltage and FS/FSE operation.
The capacitor ensures the trim will transition to the correct locked/unlocked state upon power loss.
Inrush currents impact the total number of M996 which can be connected to a power supply.  The limits primarily impact Fail Secure M996L.

How Many M996L Can Be Operated On An Allegion Power Supply?
 

Fail Safe Operation:

Because of  minimal inrush current, the power supply can operate a quantity of M996 based on the calculation :   PS Current / Inrush Current.

Quantities shown in the following table are conservative. 

For quantities greater than 10,  please contact Product Support to review any other considerations for the application.

  12VDC 24VDC
     
PS902 10 10
PS904, PS914 20 20
PS906 30 30

 

 

Fail Secure Operation

  12VDC 24VDC
     
PS902 * 2 4
PS904, PS91 * 4 8
PS906 * 6 12
     
PS902 x 4RL  **
PS904, PS914 x 4RLx4RL  ** 8
PS906 x 4RL  x 4RL x 4RL ** 12  12

*    With no option board or 4R board (no sequencing) ,  quantities shown are maximum allowed per supply. This assumes possibility of simultaneous operation.
**  With 4RL option  board sequencing, additional trim can be operated per supply.  Quantities shown assume one trim per output.
     Higher quantities possible with 2 trim per output.  Please contact product support to review applications exceeding quantities shown. 

 

How Many M9996L Can I Connect To non-Allegion Power Supplies?

Testing has not been done on any power supplies by other manufacturers.

General guidance is that  the total inrush current should under power supply maximum rating. However, Allegion can not confirm quantities or performance using other supplies.

 

Product Support Phone Number: 877-671-7011,  option 2,  then option 3.