How do you wire up an M490DE to a 900-4RL with a FA on it so it will drop power in a fire alarm condition?

Any powered outputs on the 900-4RL will lose power if the FA board on the 900-4RL opens, use a dry relay to trigger release input, the Maglock should be on NO1 and C1 and a jumper on I1 and SC.

Please review with product support at 877-671-7011,  option 2.   Fire alarm contacts are normally connected directly to the M490DE. 


DISCLAIMER:

INFORMATION PROVIDED THROUGH THIS SITE IS PROVIDED TO YOU AS IS WITHOUT ANY EXPRESS REPRESENTATIONS OR WARRANTIES OF ANY KIND, AND WE MAKE NO REPRESENTATION OR WARRANTY THAT THIS SITE(OR ANY INFORMATION PROVIDED IN RESPONSE TO YOUR INQUIRY), WILL BE ACCURATE, COMPLETE, OR ERROR-FREE.

YOU AGREE THAT YOU MUST EVALUATE ALL INFORMATION AND RESPONSES, AND THAT YOU BEAR ALL RISKS ASSOCIATED WITH, THE USE OF THIS SITE, INCLUDING ANY RELIANCE ON THE ACCURACY,COMPLETENESS, OR USEFULNESS OF ANY INFORMATION OR MATERIALS MADE AVAILABLE THROUGH THIS SITE.