How do you wire a Sr. Swing into the fire alarm system when you want the door to hold open all the time and close with fire panel signal?

The fire alarm contact (N.C.) must be wired in the 120VAC power feed to remove power from the Sr. Swing to allow it to close with a fire alarm signal. The hold open signal will have to be removed and reapplied after the fire alarm system is reset before the operator will function again. The Sr.Swing has to re-learn after power is restored.