How do I connect the external inhibit option for the Chexit?

For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire connector of the Chexit device. 

For Chexit devices shipped prior to 8-24-2015 with solenoid driven connect your normally closed contact from access control system between green and white or green and red on the ten wire connector of the Chexit device.