Von Duprin RX Switch Detail

RELATED FAQS

Question
Answer
The attached table shows the part numbers for LX-RX and LX-RX-LC switches field installed.
Cylinder dogging (CD) and an RX switch can be ordered together with 33/35 or 98/99 series.
This can be done ONLY with non fire rated exit devices.
RX switch is request exit and LX switch is latch bolt monitor switch. They do not required a power supply directly. The electrified hardware that RX or LX switch conne...
Von duprin will supply the 996L and 996L-BE trims with RX switch. Von Duprin will not supply the 996L-NL and 996L-DT trims with RX switch because the switch monitors the lever movement and the leve...
If the RX switch is in the device itself yes. You can not however have both the "E" and "RX" options in the same 996L trim as both the solenoid & switch are mounted in the same place in the trim.
The Von Duprin RX996L trim was released to standard order entry in May 2010. The Von Duprin 996L and 996L-BE trims can be ordered with RX switch. The 996L-NL and 996L-DT trims can not have the...
The RX-LC and LX-LC (Low Current) switches are used for current up to 0.05 amps at 24 VDC and the standard RX and LX switches are used for current greater than 0.05 amps up to 0.5 amps at 24 VDC.
Here is detailed information on why the Von Duprin RX-LC Swtich is required by the AD300 and AD400 993 units.   A low current switch is needed because … -     &nb...
ALK kit comes with standard RX switch. It can be ordered without the RX switch or with LX switch as an option.
The devices baseplates/scissor assemblies are different and will not accept the Von Duprin RX switch.
The RX monitors the push bar while the LX monitors the latch bolt of the exit device. A SS device has an LX and a key cylinder switch plus an emergency push bar signage.
The RX switch is required to activate the ALK. The RX switch monitors the pushbar and will signal the ALK to go into alarm when the pushbar is depressed. The RX switch also allows free in...