vertical rod device with bottom latch only

RELATED FAQS

Question
Answer
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
Hardware falling off a door is caused by one or all of the following issues: Field abuse Improper internal reinforcements in the door Improper field preparation The top or bottom rod case can...
The extension rod could be used either on the top or bottom rods.
The following items may cause the exit devices top latch from being held in the retracted position. 1. The top or bottom rods are out of adjustment. 2. The top latch hold back...
Following exit devices 2227/F, 33/3527A/F, 33/3547A/48A/F, 98/9927/F and 98/9947/48/F have similar rod adjustment procedures. All top latches control the bottom latch assemblies. When do...
Installation should be 6" from bottom of the door. See attached templates as reference.  T-5494 for HM Doors W-5494 for Wood Doors
Following parts are required to add the bottom rod and latch to the 98/9927-LBR device.  Bottom Rod: 050515 for 9827 and 050514 for 9927 (specify finish)  Bottom Latch Assembly: 05009...
One of the following items may cause the EL1490 device to retract then release: Incorrect power supply - Verify you have the PS873-2/4TD or PS914-2RS/4RL power supply. Problems with wire gauge...
The internal rods and latches for the 25-C carried over from the older 18-C device so they can be used interchangeably.