test von duprin module

RELATED FAQS

Question
Answer
For Potted Modules shipped before August of 2012, you can test by applying power to the potted circuit breaker to and if good the following voltages will be seen: 23-24V DC on the gree...
The circuit board is sometimes referred to as a "module" in the field.
The power to the Von Duprin potted module also called potted circuit breaker is non polarized.
Part number for Von Duprin standard 15 sec. release Chexit module shipped after 8-24-2015 with motor driven is 040086-00. Part number for Von Duprin standard 15 sec. release Chexit module shi...
The best way to test the Von Duprin EL solenoid is with an ohm meter. You must test both coils to make sure the solenoid is good. The coil has three wires; green, yellow, and orange. The green wire...
Following could cause the fuse to blow in Von Duprin PS873 power supply. PS873 power supply provides 2AMP at 24VDC or 4AMP at 12VDC. If this limit is exceeded the fuse will blow in the power sup...
Auxiliary fire latch is tested only from door to door latching by Von Duprin. Some door manufacturers have tested our devices LBR and use additional fire latches to pass the fire test. Contact the ...
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven. Related Solution: What wire&n...