Allegion
Terms of Use
Privacy Policy
Frequently Asked Questions
Ask your question
Entering your question as a complete sentence will provide more accurate results than keywords or phrases.
User questions
FAQs
Category List
“
Solenoid pulls and releases
”
RELATED FAQS
Question
Answer
EL Device Troubleshooting Guide
Resolution:
VISIT US.ALLEGION.COM/EL-SUPPORT FOR TROUBLESHOOTING VIDEO, DOWNLOADABLE GUIDE, AND INSTALLATION INSTRUCTIONS(For best viewing, use Chrome or Firefox browser.)ALLEGION EL SOLENOID ELECTRI...:
What could cause the Von Duprin EL solenoid not to hold when mechanism cover plate is slide over the solenoid?
Resolution:
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment. You must lengthen the rod by turning the hex nut in front of the plun...:
What would cause an EL device to pull and release?
Resolution:
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...:
What wire gauge and run is recommended for Von Duprin electric latch retraction EL device?
Resolution:
:
What would cause an EL exit device to pull and release repeatedly?
Resolution:
Following could cause the EL device to pull and drop repeatedly. Short to ground on EL wiring. Incorrect wire gauge used. For wire run and gauge requirements, click HERE Wrong power suppl...:
Why is my Von Duprin CX going into a weak alarm after the rearm delay?
Resolution:
Chexit devices shipped prior to 8-24-2015 with solenoid - the solenoid pulls and drops, the alarm sounds, there is a solid LED or no LED light after the rearm t...:
Solenoid on Chexit pulls back and immediately lets go and alarm goes off with red solid light.
Resolution:
The following could cause the Chexit solenoid ( devices shipped prior to 8-24-2015) pulls in then drop out with no alarm. Mechanical adjustment such as vertical rods. Disconnect t...: