RX vs RX-LC switch

RELATED FAQS

Question
Answer
The RX switch is activated at approximately 18 degrees of lever rotation. 
Here is detailed information on why the Von Duprin RX-LC Swtich is required by the AD300 and AD400 993 units.   A low current switch is needed because … -     &nb...
The RX-LC and LX-LC (Low Current) switches are used for current up to 0.05 amps at 24 VDC and the standard RX and LX switches are used for current greater than 0.05 amps up to 0.5 amps at 24 VDC.
The attached table shows the part numbers for LX-RX and LX-RX-LC switches field installed.
Supply wires - 22AWG
RX wires - 22AWG
LX wires - 22 AWG