The attached table shows the part numbers for LX-RX and LX-RX-LC switches field installed.
Here is detailed information on why the Von Duprin RX-LC Swtich is required by the AD300 and AD400 993 units.   A low current switch is needed because … -     &nb...
The RX-LC and LX-LC (Low Current) switches are used for current up to 0.05 amps at 24 VDC and the standard RX and LX switches are used for current greater than 0.05 amps up to 0.5 amps at 24 VDC.
PN33/35/98/99 Pneumatic exit devices are not usually used with RX or LX switches since the Pneumatic PN device is used instead EL to eliminate the electric from the device.
The hole should be drilled in the field once the end cap is located on the door.  It is a 5/8" hole, that is located 5/16" from the end of the mechanism case. See installation instruction of t...
The RX monitors the push bar while the LX monitors the latch bolt of the exit device. A SS device has an LX and a key cylinder switch plus an emergency push bar signage.
The Von Duprin RXLX combination switch must be ordered together as one assembly. Existing RX or LX switch must be removed to install the combination RX LX switch. Make sure correct RX LX combinatio...