resistance on el solenoid

RELATED FAQS

Question
Answer
Only applicable for solenoid driven Chexit devices shipped from the factory prior to 8-24-2015; Chexit solenoid coil resistance between the green and orange wires is 110-140 ohm and betw...
The threaded bushing on the solenoid plunger requires 8-9 threads showing to operate correctly.
The new motor driven ND electrified locks shipped after March 14, 2016 do not require a solenoid. The Schlage ND-Series electrified locks shipped prior to March 14, 2016 would have used a...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
The best way to test the Von Duprin EL solenoid is with an ohm meter. You must test both coils to make sure the solenoid is good. The coil has three wires; green, yellow, and orange. The green...
To check an ME or SE solenoid Unplug the solenoid from the circuit board. Measure resistance across the 2 pin of the solenoid connector. The solenoid resistance should read: 24 volt solenoi...
The resistance readings for a Falcon 24 or 25 Series EL solenoid should read;Green to Yellow = Pull Coil, should measure between 1 and 2 ohms of resistance. Green to Orange = Hold Coil, s...