maximum transom glass size

RELATED FAQS

Question
Answer
Yes. 1 7/16" thick glass but a special rabbet size is required. The size of rabbet required for the frames would depend on the size of the glazing bead being used. For 1" wide glazing stops, ...
Maximum glass light size for a 90 minute (1 1/2 hour) door depends on the type of glass being installed. Wire glass = 100 square inches is max exposed glass when wire glass is used. Note - ma...
DW-Series Fire Rated Borrowed Lights are available in the following sizes: 60 minute (1 hour) rating = 2721 square inches of visible glass. maximum frame rabbet to rabbet dimensions = 78 1/4...
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...
Glass lights are available in fire rated T-Series doors: Limited to one (1) light per door leaf with a maximum of 100 square inches of exposed glass. This applies to all hourly ratings a...
Maximum hourly rating for a transom and side light or panel frame is 1 1/2 hour (90 minutes). In masonry wall application the maximum is 13'6" x 12'2" In stud wall application the maximum is 13...
The following size limitations per frame unit, are in enforced for welded elevation frames shipped from the factory. These limitations are in place due to the physical size of shipping tr...
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design. A14-Series door construction: Max fire rating is 20 minute. UL label only FG must use Over-Lapping Stee...
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...