maximum dimension for wire glass

RELATED FAQS

Question
Answer
DW-Series Fire Rated Borrowed Lights are available in the following sizes: 60 minute (1 hour) rating = 2721 square inches of visible glass. maximum frame rabbet to rabbet dimensions = 78 1/4...
Glass lights are available in fire rated T-Series doors: Limited to one (1) light per door leaf with a maximum of 100 square inches of exposed glass. This applies to all hourly ratings a...
Maximum glass light size for a 90 minute (1 1/2 hour) door depends on the type of glass being installed. Wire glass = 100 square inches is max exposed glass when wire glass is used. Note - ma...
Maximum glass light sizes for 3 hour fire doors is as follows: Wire glass - not approved for use in 3 hour fire doors. Ceramic glass: UL & ITS/WH allow one (1) light with 100 square inc...
On fire rated transom and/or sidelight frames and fire rated window frames, Steelcraft labeling procedures only control the O/A width and/or height of the frames based on wall condition. The amount...
A UL 20 minute fire rating is the maximum fire rating for a Full Glass (FG) door design. A14-Series door construction: Max fire rating is 20 minute. UL label only FG must use Over-Lapping Stee...
When dealing with glass lights in doors, there are three (3) critical dimensions which must be coordinated: Exposed Glass Size (EGS) - the horizontal and/or vertical dimensional size of the vision...
Minimum dimensions to cutouts for glass lights: Vertical edge of door to edge of cutout = 5 29/32" Top of door to top of cutout = 6" Bottom of door to bottom of cutout = 10" Reinforcing chann...
Dutch doors are available as Fire Rated door assemblies and have similar component requirements as a single leaf fire door. Exceptions are as follows: The Dutch Door assembly must have a lock...