Question
Answer
Is the Von Duprin 1609 strike fire rated for pairs of doors?
Resolution:
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F,...:
Is the Von Duprin 6223 fire rated for pairs of wood doors?
Resolution:
The 6223-FSE electric strike is fire rated for pairs of wood doors, but check with wood door manufacturer to see if they have been approved for this application.:
What strike do I use with a Von Duprin rim device on a pair of doors with flush bolts?
Resolution:
NON Fire Rated doors would use the 1609 strike applied to the inactive leaf with flushbolts. This may NOT be used on Fire Rated openings.:
Can we have 9927-F LBR and 9975-F on a paired opening?
Resolution:
This combination is not available. The 98/9927-LBR-F has only been UL tested as vertical by vertical combination on pairs of fire rated doors.:
Can I use the 990 DT trim with a fire rated device?
Resolution:
The 990DT trims are not recommended on fire rated openings. Since you cannot dog the device and the device is not electrified you are inviting people to pull on a door that will not open and possib...:
Which strike do you use with an XP98/99 device?
Resolution:
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.: