Is there EL troubleshooting?
”
RELATED FAQS
Question
Answer
Will the MPB-842 or MPB-840 power EL or QEL devices?
Resolution:
The old MPB842 power supply will power up to two EL electric panic bars but will not power the QEL devices. A defective potted module inside the electric panic bar or defective power supply coul...:
What are the Von Duprin part numbers for RX, LX and RX,LX-LC switch kits for field installation?
Resolution:
The attached table shows the part numbers for LX-RX and LX-RX-LC switches field installed.:
Is the power to the Von Duprin potted module polarized?
Resolution:
The power to the Von Duprin potted module also called potted circuit breaker is non polarized.:
Is the EL wiring adapter needed for QEL?
Resolution:
The EL wiring adapter is not needed for QEL devices.:
What is the part number for the ND solenoid?
Resolution:
The new motor driven ND electrified locks shipped after March 14, 2016 do not require a solenoid. The Schlage ND-Series electrified locks shipped prior to March 14, 2016 would have used a...:
How do I wire an EL device to normally hold open the latch and release it during a fire alarm?
Resolution:
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted. During a fire alarm, the contact will open, dropping...:
Can an EL device be ordered Fail Secure?
Resolution:
This is not possible as an EL device is an electric latch retraction and requires power to unlock the door thus only available in Fail Secure.:
Will the 900-2Q option board operate an EL device?
Resolution:
The 900-2RS is recommended to be used with EL devices but if you have a 900-2Q with PS914 power supply it can be used to operate up to two EL or one EL and one QEL devices .:
How do you test a Falcon 24 or 25 Series EL solenoid?
Resolution:
The resistance readings for a Falcon 24 or 25 Series EL solenoid should read;Green to Yellow = Pull Coil, should measure between 1 and 2 ohms of resistance. Green to Orange = Hold Coil, s...:
Is there a wiring diagram for EL and Von Duprin PS914-2RS power supply?
Resolution:
Reference The 914 Installation instructions.:
Why do you need the potted circuit breaker for the Von Duprin EL device?
Resolution:
The potted circuit breaker for the Von Duprin EL device does the switching from the 16 amp pull coil on the solenoid to the .33 amp holding coil of the solenoid.: