Question
Answer
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock.
Astragal must be applied to pull side of active leaf, since placing the stragal on the inside of the inactive leaf will interfere with the active door closing.
Inactive Door, Wde Inactive
Ives SB360 surface bolt at top and bottom are the only flush bolts approved for use on H-Series hurricane FBC or NOA applications? The only approved latching hardware for inactive leaf of pairs w...
For non fire rated doors only the 1609 strike would be used on the inactive leaf that is flush/surface bolted or with a *surface or concealed vertical rod device on other door leaf.
Astragals are required on: 3 hour fire rated pairs: Double doors - swinging in the same direction Double Egress - swinging in opposite directions Fire rated Dutch Doors Fire rated 1 3/4" t...
There are 2 types of door coordinators available: Bar Coordinators (Ives COR Series): Surface mounted to the bottom surface of the frame soffit. The active door lever, located nearest to th...
With a mullion: Use the standard strike 267 With no mullion and inactive leaf being held closed with flush or surface bolts: Use the 2609 double door strike