Height for fire bolt installation
”
RELATED FAQS
Question
Answer
Where do I install my Auxiliary Fire Latch (AFL) in a Less Bottom Rod, Fire Rated (LBR-F) exit device?
Resolution:
Installation should be 6" from bottom of the door. See attached templates as reference. T-5494 for HM Doors W-5494 for Wood Doors:
What height should a lock or deadbolt be installed?
Resolution:
According to ANSI specifications for cylindrical or mortise locks: The lock strike centerline should be 40 5/16" from the bottom of the frame with the lock in relation to the strike.&...:
Can a filler or cover plate be used to blank out a EPT prep on a fire rated frame?
Resolution:
Yes, a filler plate can be used to cover an EPT prep as long as it is made from the same material as the frame. This information can also be found in NFPA 80 under Chapter 5 for Field Modifications.:
How many compression anchors are provide per jamb on DW-Series frames?
Resolution:
For compression anchor details refer to the “ANCHORING SYSTEMS” section in the Steelcraft Tech Data Manual.Anchor Quantities: • 1 compression anchor per jamb through 9"depth • ...:
What is the part number for the former F588 from Monarch?
Resolution:
The top latch for a Fire rated surface vertical rod device is part #650375-00 which replaced the old part #F588.:
At what degree will the AFL (Auxiliary Fire Latch) bolt release?
Resolution:
1400 degrees which is approximately 20 minutes after the fire starts.: