handle gets hot

RELATED FAQS

Question
Answer
If the solenoid of the 6000 series electric strike is powered continuously with proper voltage at room temperature, the solenoid can reach 200-220 degree Fahrenheit.
It is normal for a solenoid to be warm to the touch.
Various situations, such as continuous duty use or application of voltage that is higher than specified, can cause the solenoid to become warm.
If there is concern that the solenoid or device is "too hot" or has the capability to cause injury, disconnect the device and contact a authorized service representative to analyze the opening.
This is usually an indicator of applying excessive voltage.  Measure the voltage going into the solenoid and make sure you have 24-26.4VDC cross the two wires going into the solenoid. Also measure ...
Followings are the steps to convert the Von Duprin 88TP to 88L device. Need to replace the back plate on the 88 exit device, part number 050103. Order a 373L trim and specify handing. Recomme...
Yes, Von Duprin 996L lever handle can be replaced with a new one . Attached installation instructions shown how to replace the existing lever handle on 994/996L trim for rim and vertical rod device...
Von Duprin Exit Devices (33A/35A, 98/99, etc) are handled on a case by case basis regarding their ability to handle salt and chemical environments. Our powder coated finishes US28 (Anodized Alum...
The pneumatic operators are designed to function with an input air pressure to the 7901/7902 Series control box of 80 (min) 100 (max) PSI, and an output pressure of 60 to 80 PSI to the pneumatic (2...