EL Wire Run

RELATED FAQS

Question
Answer
For Product Shipped Prior to August 2012 using the old (black) potted module:a.       0-100 ft 14 gauge wireb.      0-200 ft 12 gauge wire&nbs...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
Product Ordered after 7/10/2012 - Product identified by label on QEL motor You no longer need to use the 900-2Q option board (no longer available) with the PS900 power supplies to ...
Product Ordered before 7/10/2012 - Product identified by no label on QEL motor. You must use the 900-2Q option board with the PS900 power supplies to operate the QEL devices.  The attached ta...
You can power both mag locks and EL devices from PS914 power supply.
It requires 900-4RL and 900-FA option boards to release the mag locks when a fire alarm is activated. Specify PS914 x 900-4RL x 900-FA.
The wires run through the device out to the EPT. See step 7 on page 5 of E996L instructions.
Followings could cause the PS914-2RS power supply to cycle on and off: Wrong gauge wire or run distance from power supply to the EL device. Click HERE for wiring requirements Over load  to the ...
It is recommended to use the Von Duprin EPT10 with CX device but if you need a door loop or electric hinge these are also acceptable. See attached table for wire run and gauge requirements: ...
Make sure the proper power supply (PS873 or PS914) and proper gauge and run wire is used for Chexit devices shipped prior to 8-24-2015 with solenoid driven. Related Solution: What wire&n...