EL stays retracted

RELATED FAQS

Question
Answer
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
The Von Duprin EL option can be added to any existing 33A/35A, 98/99 series exit devices. 
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
Most likely need to length the top rod so latch can engage it's internal latch retention state. See 2390 Instructions for adjusting rod lengths.
Yes the Von Duprin QEL exit device retracts the latch bolt and pushpad. Pushpad and latch bolt stay retracted as long as power is applied to the QEL exit device.
The following items may cause the exit devices top latch from being held in the retracted position. 1. The top or bottom rods are out of adjustment. 2. The top latch hold back...
Following exit devices 2227/F, 33/3527A/F, 33/3547A/48A/F, 98/9927/F and 98/9947/48/F have similar rod adjustment procedures. All top latches control the bottom latch assemblies. When do...
Check the adjustment and if this does not resolve then you may possibly have a defective center case or bottom latch.
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...