El exit device requirements

RELATED FAQS

Question
Answer
The conversion kit does not contain a new mechanism case cover plate.  If a cover plate is desired you would need the Fire or Less Dogging Cover Plate for EL conversion kit and panic cover plate fo...
Current EL and QEL baseplate conversion kits can be used on all latching types of the 33/35 series (non "A" version which were manufactured prior to 2003).  At one time, the obsolete black EL ...
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
For devices shipped after 8-24-2015 with motor driven:  a.       0-200 ft, use  #18 gauge wire b.      0-500 ft, use #14 gauge wir...
For Product Shipped prior to 8-24-2015 with solenoid driven:          a.       0-100 ft, use #14 Gauge Wire      b.&n...
  For Product Shipped Prior to August 2012 using the old (black) potted module: a.       0-100 ft 14 gauge wire b.      0-200 ft 12...
 
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...
No, Von Duprin exit alarm ALK and electric latch retraction QEL or EL are installed in the same location and can't be ordered together with the same device.
SD is Special cylinder dogging in the center case of 98/99 rim and vertical rod non fire rated devices and is available with standard, EL, QEL, CX and ALK.