delayed egress with auto operator pair

RELATED FAQS

Question
Answer
Use the PS902-2RS power supply with LCN auto operator on single door, PS904-2RS power supply on double door and PS904/906-2RS-2RS for 2 pair of QELA is required for basic operation with a...
The overhead concealed operators (2850/2860) will not work on a Double Egress frame because the doors are not in the same plane. You will have to use the surface mount (9553 / 9563) on Double Egres...
One Deleay Egress Controller (DE5101) can run two mag locks on a pair of doors, provided the doors are not controlled independently
 Pneumatic Automatic Operators are used in areas where electrically operated devices are not convenient or permitted.  Consists of a modified, heavy-duty door closer for manual oper...
This is not possible.  Due to the device's 16 Amp in-rush it would require it's own PS914-2RS which will power 1 or 2 devices.
The 4630/4640 Series operator is designed/recommended for a door that will see mostly manual traffic with the occasion automatic/ handicap operation.
The 4610/4620 series operators are obsolete. There is no replacement part for any electronic component (motor/clutch, controller, input/output PC boards) for the obsolete 4610/4620 operators.Essent...
The capabilities of the auto operator and the required operation of the opening will affect the selection of a power supply.
The 900-4RL has two out put for EL devices and signals to the auto operators to open the doors. PS914 power supply is required with 900-4RL option board to operate the EL device and auto operato...
Von Duprin PS914 x 900-4RL supports two EL with two auto operator.
Chexit devices are NOT electric latch retraction.  In order for Chexit device to operate with an auto operator you will need to add a rim electric strike on a single door or a pair o...