chexit device outside access for card reader

RELATED FAQS

Question
Answer
When CX99L-BE is not armed with key cylinder on the device or shunted by card reader, the exterior 996LBE lever trim will release.
The standard Von Duprin mechanical or electrical 98/99/33/35 exit devices can not be converted to a CX98/99 or CX33/35 device. Von Duprin CX98/99 or CX33/35 has a different base p...
The access control system should provide Common and Normally Closed dry contact that will connect between the green and white wire on the CX 10 wire harness.
If an access control system is not available to test the card output on a hand reader, this card emulation test can be done to verify the card format is correct.  These steps will guide you in...
For Chexit devices shipped after 8-24-2015 with motor driven connect your normally closed contact from access control system between green and red on the twelve field wire ...
Chexit devices shipped prior to 8-24-2015 with solenoid driven: A normally closed card reader contact, key pad contact or any other control contact connects to the Green an...
The PS914 x 900-2RS option board doesn't have time delay. If time delay is required specify PS914 x 900-4RL. 900-4RL provides up to 75 seconds, 5 second  increment unlock time.