can EL devices be held continually retracted

RELATED FAQS

Question
Answer
If mechanism cover plate causes the EL solenoid to drop when slid over the solenoid, the solenoid plunger requires adjustment.  You must lengthen the rod by turning the hex nut in front of the plun...
The Von Duprin EL option can be added to any existing 33A/35A, 98/99 series exit devices. 
The Von Duprin PS914 power supply must be used on the EL devices with either the 900-2RS or 900-4RL option board since the EL devices requires power supplies set at 24VDC to be able to provide the ...
  You can use a Von Duprin PS914 power supply with any of the following option boards depending on the application. 900-2RS board  will power 1 or 2 devices that do not require timing from pow...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
The Falcon EL devices can be operated in a continuous duty cycle.
The following items may cause the exit devices top latch from being held in the retracted position. 1. The top or bottom rods are out of adjustment. 2. The top latch hold back...
Following exit devices 2227/F, 33/3527A/F, 33/3547A/48A/F, 98/9927/F and 98/9947/48/F have similar rod adjustment procedures. All top latches control the bottom latch assemblies. When do...
If your Von Duprin EL (solenoid) device pulls and releases quickly instead of holding the latch retracted, please check all of the items below.In most cases, one or more of these solutions will r...