What ES is used on paired doors
”
RELATED FAQS
Question
Answer
What electric strike can be used on a pair of doors with an L9000 lock?
Resolution:
Von Duprin 6223 electric strike is the most common closed back strike or the 6221 for open back strike on inactive leaf that can be used with Schlage L9000 or Von Duprin 7500 mortise lock.:
Can the Von Duprin 5100 electric strike be used on a pair of doors?
Resolution:
The following application information apply to the 5100 electric strike: Can only be used on a single door with a cylindrical lock Can not be used on a pair of doors Can not be used on a mullion:
What strike is used for in-active leaf on pair of doors with 19-R?
Resolution:
The 571 strike is used on the in-active door leaf of a pair or on the 19-V door leaf when both doors are active per template.:
Can the electric strike be used with a vertical rod device on a fire-rated door?
Resolution:
Not for use in fire rated openings.:
Which strike do you use with an XP98/99 device?
Resolution:
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.:
Can we have 9927-F LBR and 9975-F on a paired opening?
Resolution:
This combination is not available. The 98/9927-LBR-F has only been UL tested as vertical by vertical combination on pairs of fire rated doors.: