What electric strike can be used with rim device on paired doors

RELATED FAQS

Question
Answer
The 6111 electric strike can be used only on non rated openings less bottom rod with pullman top latch (use ES prefix when ordering device). Device back set will change to match the centerline of t...
Not for use in fire rated openings.
NON Fire Rated doors would use the 1609 strike applied to the inactive leaf with flushbolts.  This may NOT be used on Fire Rated openings.
The 22, 33/35A and 98/99 rim exit devices: The 6111 is the most common electric strike to be used with these devices 6112 and 6113 electric strikes also could be used The 6300 surface mount el...
The backset for a 98/99 rim PANIC device with 1609 strike is 2 3/8" from center of the opening to center line of the device. See template
The Von Duprin 1609 cannot be used on a pair of fire rated doors. We recommend using the Von Duprin fire rated mortise exit device in lieu of the rim device such as the Von Duprin 5575-F,...
The 909 strike is used in single and paired non-fire rated and single fire rated openings.  The 954 strike is used in fire rated paired openings.
The 1609 strike cannot be used with Von Duprin XP98/99 exit device.