Senior Swing Fire Alarm contacts

RELATED FAQS

Question
Answer
Fire alarm contact would tie right into the Von Duprin Chexit device not to the PS914 power supply. There is no requirement to install the fire alarm board.
 The Basic PS914 power supply will not accept a 900-FA fire alarm board. 900-8F option board is required with PS914 power supply to accept 900-FA fire alarm board (900-8F is an adaptor board for...
The "Fire Alarm" indication occurs when there is no connection across terminals 13 & 14. Check to verify that the "Fire Alarm" shunt (R1 jumper) on the I/O board has not been cut. Install jumpe...
The following are needed for a basic installation: Fire alarm contact is always required with Von Duprin Chexit device. 1 1/4" Mortise cylinder with straight cam is required to turn&n...
The following items may cause the  PS900 series power supply to have no DC output voltage. 1. If  the DC voltage selection jumper is missing, the power supply will not provide any D...
To keep the Von Duprin electric latch retraction EL or QELA exit device dogged (retracted) all day, have your access control, Key pad, key switch, fire alarm contact or any other signals ...
Chexit motor driven devices shipped after 8-24-2015:You can use 1 Chexit device with PS902, 3 Chexit devices with PS904, and 4 Chexit devices with PS914 or PS906 power supplies with proper gau...
Use a normally closed fire alarm as the input to the power supply option board (PS873-2 or PS914-2RS), this will hold the latch retracted.  During a fire alarm, the contact will open, dropping...
For Allegion's recommendation see here.
The 8310-877 Bodyguard Safety Sensor attaches (plugs in) to the P1 connector on the Senior Swing controller. The 8310-846 (761462-00) wiring harness "included" with the 8310-877 safety sensor is us...
Senior Swing 9540 Regular, push side arm, part number is: 9540-3077, specify hand and finish. Senior Swing 9550 Regular, push side arm, part number is: 9550-3077, specify hand and finish. Senio...
The part number for the threaded rod "only" on the Senior Swing regular arm is 9540-82, 9550-82, or 9560-82 or -82L for the long rod option.The part number for the threaded rod, turn buckles, and m...
The companion cable can be ordered as a 9550-982 or a 2850-982, the same cable is used on both models.
The current (digital control box) activation input wiring harness (# 761464-00) is included in the Sr. Swing parts bag (-518), and has 4 wires in it, Black, White, Yellow, & Gray. This harness p...
The Senior Swing control box is ordered as a 95xx-3462. Example - 9530-3462, 9540-3462.
The Senior Swing Series changed to the "Digital" control box in Sept. of 2006.
The Senior Swing has an optional (plug in) Off/Auto/Hold Open switch available. The 8310-806R (rocker switch), or 8310-806K (key switch). CANNOT use switch by others, requires a special (center - n...
The Von Duprin Chexit device will not automatically rearm itself after a fire alarm clears.  After a Fire Alarm has triggered the Von Duprin Chexit device, the device must be manually reset&nb...